Software is not developed by BlueWalker GmbH.
There was no Linux software available for the PowerWalker PDU and ATS, but the manufacturer was kind enough to supply me with what I needed to make my own library.
I'm using a Raspberry Pi as a power manager in my homelab, it is connected to both the PDU and ATS. It's best practice to have a single application responsible for communicating with the devices, as you will get communication errors if two applications tries to talk to the same device at the same time.
I am using the mqtt.py
script to publish ATS and PDU data on the MQTT network. Then you can have multiple clients subscribe to the respective MQTT topics, like Home Assistant. To visualize the data I use the Home Assistant InfluxDB component, then Grafana pulls the data from InfluxDB and makes cool graphs.
To make sure that the mqtt.py
script keeps running; I'm using Supervisor.
Note! Methods and keys may change; as I am still investigating use cases and best practices.
Connect either the USB or the serial port, find the correct device path and instantiate.
import powerwalker
pdu = powerwalker.PDU("/dev/ttyUSB0")
ats = powerwalker.ATS("/dev/ttyUSB1")
There's a chance that your device is not being recognized as usbserial. Therefore, you have to instantiate as usbhid device:
import powerwalker
pdu = powerwalker.PDU("/dev/hidraw0", usbhid=True)
ats = powerwalker.ATS("/dev/hidraw1", usbhid=True)
Give regular users in the dialout
group access to hidraw
devices:
Add this line to /etc/udev/rules.d/99-com.rules
:
KERNEL=="hidraw*", GROUP=="dialout", MODE="0664"
And run sudo udevadm trigger
PowerWalker PDU RC-16A is designed to distribute AC power from a single source to 8 outputs with advanced load monitoring and local or remote ON/OFF switching control of individual outlets.
https://powerwalker.com/?item=10133001
Method | Description | Type |
---|---|---|
connect() |
Connect to PDU device. | - |
send(cmd) |
Send custom command. | - |
info() |
Get and return device information. | get |
status() |
Get and return device statuses. (see codes below) | get |
power_w() |
Get and return active power (W) measurements for input and all outputs. | get |
power_va() |
Get and return apparent power (VA) measurements for input and all outputs. | get |
energy_kwh() |
Get and return energy consumption (kWh) for input and all outputs. | get |
energy_kwh_clear() |
Clear energy consumption values for input and all outputs. | set |
countdown_times() |
Get and return shutdown and restore countdown times for all outputs. | get |
shutdown(idx, shdn) |
Shutdown output idx in shdn minutes. |
set |
shutdown_restore(idx, shdn, rst) |
Shutdown output idx in shdn minutes, restore power after rst minutes. |
set |
shutdown_cancel(idx) |
Cancel pending shutdown on output idx . |
set |
protocol() |
Get and return device protocol ID. | get |
firmware() |
Get and return device firmware version. | get |
test() |
Test PDU device, turn on all LEDs and the buzzer for 5 seconds. | set |
memory_get(adr) |
Get and return memory setting at adr location. |
get |
- Off
- On
- Shutdown active
- Shutdown imminent (S01-S08 code)
- Restore active
- Overload alarm (F01-F08 code)
- Locked (L01-L08 code)
idx
: output;1
to8
,A
for all.shdn
: shutdown delay in minutes;0.1
to0.9
,1
to99
,0
for immediate.rst
: restore delay in minutes;1
to9999
,0
for 1 second.
Adr | Key | Unit | Min | Max | Default |
---|---|---|---|---|---|
0 | output_start_up_delay |
sec | 0 | 240 | 1 |
1 | out1_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
2 | out2_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
3 | out3_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
4 | out4_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
5 | out5_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
6 | out6_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
7 | out7_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
8 | out8_current_alarm |
0.1 A | 0.5 | 4.0 | 2.0 |
9 | low_input_voltage_alarm |
V | 184 | 207 | 196 |
10 | high_input_voltage_alarm |
V | 242 | 264 | 253 |
11 | max_input_voltage_shutoff |
V | 253 | 300 * | 276 |
12 | low_input_current_alarm |
0.1 A | 0.0 | 15.0 | 0.0 |
13 | high_input_current_alarm |
0.1 A | 1.0 | 16.0 | 16.0 |
14 | shutdown_imminent_signal |
min | 1 | - | 3 |
* 0xFFFF = disabled
Memory address 1 to 8 also contains output configuration byte, key: out?_config
.
Byte | Dec | Description | 0 |
1 |
---|---|---|---|---|
0 | 1 | Output status at power on | off | on |
1 | 2 | Automatic disconnection of the output 1 minute after the overload alarm | enabled | disabled |
2 | 4 | On/off button enabled on front panel | disabled | enabled |
3 | 8 | Not in use | - | - |
4 | 16 | Not in use | - | - |
5 | 32 | Not in use | - | - |
6 | 64 | Not in use | - | - |
7 | 128 | Not in use | - | - |
ACK
if command was accepted.NAK
if command was not accepted.
{ 'in_out_phase': '1/1',
'in_socket_no': '1',
'model': '############PDU',
'nom_in_voltage': '230',
'nom_out_voltage': '230',
'out_socket_no': '8'}
{ 'in_current': 2.1,
'in_freq': 49.8,
'in_voltage': 225.5,
'int_temp': 36.0,
'out1_current': 0.4,
'out2_current': 0.5,
'out3_current': 0.3,
'out4_current': 0.1,
'out5_current': 0.2,
'out6_current': 0.2,
'out7_current': 0.3,
'out8_current': 0.0,
'status': { 'a01_low_in_voltage': 0,
'a02_high_in_voltage': 0,
'f09_low_in_current': 0,
'f10_high_in_current': 0,
'f11_pwr_fail_aux1': 0,
'f12_pwr_fail_aux2': 0,
'na_b8': 0,
'na_b9': 0,
'out1_status': 1,
'out2_status': 1,
'out3_status': 1,
'out4_status': 1,
'out5_status': 1,
'out6_status': 1,
'out7_status': 1,
'out8_status': 1}}
{ 'in_w': 441,
'out1_w': 62,
'out2_w': 108,
'out3_w': 74,
'out4_w': 37,
'out5_w': 39,
'out6_w': 33,
'out7_w': 57,
'out8_w': 0}
{ 'in_va': 478,
'out1_va': 108,
'out2_va': 123,
'out3_va': 83,
'out4_va': 47,
'out5_va': 43,
'out6_va': 65,
'out7_va': 70,
'out8_va': 0}
{ 'in_kwh': 725.9,
'out1_kwh': 4.3,
'out2_kwh': 103.4,
'out3_kwh': 17.4,
'out4_kwh': 114.0,
'out5_kwh': 201.9,
'out6_kwh': 106.8,
'out7_kwh': 47.6,
'out8_kwh': 19.8}
{ 'out1_cd_sec': {'r': 0, 's': 0},
'out2_cd_sec': {'r': 0, 's': 0},
'out3_cd_sec': {'r': 0, 's': 0},
'out4_cd_sec': {'r': 0, 's': 0},
'out5_cd_sec': {'r': 0, 's': 0},
'out6_cd_sec': {'r': 0, 's': 0},
'out7_cd_sec': {'r': 0, 's': 0},
'out8_cd_sec': {'r': 0, 's': 0}}
{'prot_id': 'PI90'}
{'verfw': 0.15}
{'output_start_up_delay': 1}
{'out1_config': 255, 'out1_current_alarm': 20}
ATS (Automatic Transfer Switch) supports connection of two independent power sources. If primary power source fails, the secondary will automatically back up the connected load without any interruption.
https://powerwalker.com/?item=10120543
Method | Description | Type |
---|---|---|
connect() |
Connect to PDU device. | - |
send(cmd) |
Send custom command. | - |
info() |
Get and return device information. | get |
status() |
Get and return device statuses. | get |
protocol() |
Get and return device protocol ID. | get |
firmware() |
Get and return device firmware version. | get |
memory_get(adr) |
Get and return memory setting at adr location. |
get |
Adr | Key | Unit | Min | Max | Default |
---|---|---|---|---|---|
0 | src1_voltage_high_loss |
V | 100 | 300 | 258 |
1 | src1_voltage_high_back |
V | 100 | 300 | 248 |
2 | src1_voltage_low_loss |
V | 100 | 300 | 180 |
3 | src1_voltage_low_back |
V | 100 | 300 | 190 |
4 | src1_freq_high_loss |
Hz | 40 | 70 | 55 |
5 | src1_freq_high_back |
Hz | 40 | 70 | 0 |
6 | src1_freq_low_loss |
Hz | 40 | 70 | 45 |
7 | src1_freq_low_high |
Hz | 40 | 70 | 0 |
8 | src2_voltage_high_loss |
V | 100 | 300 | 258 |
9 | src2_voltage_high_back |
V | 100 | 300 | 248 |
10 | src2_voltage_low_loss |
V | 100 | 300 | 180 |
11 | src2_voltage_low_back |
V | 100 | 300 | 190 |
12 | src2_freq_high_loss |
Hz | 40 | 70 | 55 |
13 | src2_freq_high_back |
Hz | 40 | 70 | 0 |
14 | src2_freq_low_loss |
Hz | 40 | 70 | 45 |
15 | src2_freq_low_high |
Hz | 40 | 70 | 0 |
16 | overload_alarm |
% | 0 | 150 | 100 |
17 | overload_fault |
% | 0 | 250 | 0 |
18 | acceptable_phases |
° | 0 | 180 | 0 |
19 | breaking_time |
ms | 0 | 9999 | 5 |
20 | blanking_time |
ms | 0 | 1000 | 4 |
{ 'battery_voltage': '---.-',
'rated_output_current': '016',
'rated_output_freq': '50.0',
'rated_output_voltage': '230.0'}
{ 'int_temp': 35.0,
'out_current': 2.2,
'out_load_pct': 14.0,
'src1_freq': 50.0,
'src1_voltage': 227.3,
'src2_freq': 50.0,
'src2_voltage': 227.3,
'status': { 'aux_pwr1_fail': 0,
'aux_pwr2_fail': 0,
'na_c0': 0,
'na_c1': 0,
'na_c2': 0,
'na_c3': 0,
'na_c4': 0,
'na_c5': 0,
'na_c6': 0,
'na_c7': 0,
'on_fault_mode': 0,
'on_src1': 1,
'on_src2': 0,
'overload_alarm': 0,
'overload_fault': 0,
'preferred_src2': 0,
'short_fault': 0,
'src1_freq_bad': 0,
'src1_voltage_bad': 0,
'src1_wave_bad': 0,
'src2_freq_bad': 0,
'src2_voltage_bad': 0,
'src2_wave_bad': 0,
'syncron_bad': 0},
'sync_angle': 1.0}
{'prot_id': 'PI97'}
{'verfw': 181.0}
{'src1_voltage_high_loss': 258}
For easy access to the device methods; use cli.py
:
$ python3 cli.py device method arguments
Run test sequence on PDU:
$ python3 cli.py pdu test
Shutdown output 8 in 0.5 minutes:
$ python3 cli.py pdu shutdown 8 0.5
Shutdown output 8 in 2 minutes, restore after 1 second:
$ python3 cli.py pdu shutdown_restore 8 2 0
Cancel pending shutdown on output 8
$ python3 cli.py pdu shutdown_cancel 8
To publish ATS and PDU data to MQTT; use mqtt.py
:
$ python3 mqtt.py
Make sure to rename config.sample.py
to config.py
and set the correct settings.
The MQTT script subscribes to cfg.mqtt['prefix'] "/pdu/outlet/ / "
; to change the state of an outlet use topic:
your_prefix/pdu/outlet/out[1-8]/set
Payload can be 0
, 1
or anything that Python casts as a boolean value.
All incoming commands are queued so not to interrupt any ongoing serial communication, at the start of each loop cycle all pending commands are performed.
Note that the state change is not immediate, there is a slight delay were the PDU warn of outlet imminent shutdown.
Also note that if an outlet is not listed in the config file as "allowed state change"; a ValueError
exception is raised.
pdu/outlet/out1 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out2 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out3 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out4 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out5 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out6 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out7 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/outlet/out8 {"shutdown_sec": 0, "state": "On", "status": 1, "restore_sec": 0}
pdu/status {"pwr_fail_aux2": 0, "low_in_voltage": 0, "pwr_fail_aux1": 0, "high_in_current": 0, "temp_c": 33.0, "low_in_current": 0, "in_hz": 49.8, "high_in_voltage": 0, "in_v": 228.2}
pdu/power/out1 {"va": 95, "w": 76, "a": 0.4}
pdu/power/out6 {"va": 0, "w": 0, "a": 0.0}
pdu/power/out7 {"va": 0, "w": 0, "a": 0.0}
pdu/power/out2 {"va": 0, "w": 0, "a": 0.0}
pdu/power/out3 {"va": 92, "w": 89, "a": 0.4}
pdu/power/out8 {"va": 0, "w": 0, "a": 0.0}
pdu/power/in {"va": 318, "w": 266, "a": 1.4}
pdu/power/out5 {"va": 65, "w": 60, "a": 0.2}
pdu/power/out4 {"va": 63, "w": 50, "a": 0.1}
ats/supply/src1 {"preferred": 1, "hz": 50.0, "bad": "0", "active": 1, "v": 229.7}
ats/supply/src2 {"preferred": 0, "hz": 50.0, "bad": "0", "active": 0, "v": 230.9}
ats/status {"out_pct": 10.0, "overload_alarm": 0, "overload_fault": 0, "out_a": 1.4, "syncron_bad": 0, "aux_pwr2_fail": 0, "sync_angle": 1.0, "temp_c": 32.0, "on_fault_mode": 0, "short_fault": 0, "aux_pwr1_fail": 0}
cli.py
: Simple command line interface.mqtt.py
: Publishing values to MQTT.ups.py
: Get UPS data fromupsc
and publish to MQTT.